DALI line planner
Checks a DALI line according to IEC 62386-101: addresses, bus current, cable length and voltage drop.
DALI limits at a glance
| Parameter | Limit per DALI line |
|---|---|
| Control gear (drivers, ballasts) | 64 addresses |
| Control devices with DALI-2 (push buttons, sensors) | 64 addresses, separate address space |
| Bus power supply current | max. 250 mA |
| Current draw per control gear | up to 2 mA |
| Voltage drop along the cable | max. 2 V |
| Cable length | max. 300 m |
Maximum DALI cable length per cross-section
The permitted length follows from the voltage drop: on the longest run between bus power supply and device, no more than 2 V may be lost – calculated with the rated current of the bus power supply, for outgoing and return copper conductors. With a 250 mA bus power supply this gives:
| Cable cross-section | Max. cable length |
|---|---|
| 0.5 mm² | 112 m |
| 0.75 mm² | 168 m |
| 1.0 mm² | 224 m |
| 1.5 mm² | 300 m (calculated 336 m) |
| 2.5 mm² | 300 m |
A smaller bus power supply allows longer runs on paper, but 300 m remains the upper limit. The planner above calculates this for your values.
How many devices fit on one DALI line?
A DALI line has 64 addresses for control gear. Depending on the operating mode, multi-channel drivers can use more than one address – the LUDC 40 W, for example, uses two in “DT6_WC” mode. With DALI-2, push buttons and presence detectors have their own address space with another 64 addresses.
The bus current must also be sufficient: 64 drivers at 2 mA each need 128 mA, and bus-powered sensors can draw considerably more depending on the manufacturer. If addresses or current are not sufficient, the installation is split across several lines.
Choosing the bus power supply
- Every DALI line needs a bus power supply – as a separate unit or built into a controller or gateway.
- A maximum of 250 mA is permitted per line, even if several supplies work in parallel.
- Check the guaranteed current in the supply’s datasheet: some units deliver up to 250 mA but guarantee less.
- A larger supply means more voltage drop by the standard, because the calculation uses its rated current, not the actual consumption.
DALI wiring: topology and cable
- Line, star and tree topologies are possible; avoid rings.
- Most DALI devices are polarity-insensitive.
- The control line may usually run together with the mains line in one cable, because DALI is not classed as safety extra-low voltage (SELV). Follow the manufacturers’ instructions.
- What counts is the longest run from the bus power supply to the farthest device.
No control cable available? The HEP+ light management system controls luminaires wirelessly.
Frequently asked questions
How long can a DALI cable be?
Up to 300 m, and no more than 2 V may be lost on the longest run. With 1.5 mm² and 250 mA the full 300 m are possible, with 0.5 mm² only 112 m.
How many devices can I connect to one DALI line?
64 control gear and, with DALI-2, another 64 control devices – provided the bus power supply current, max. 250 mA, is enough for all of them.
What is the difference between DALI-2 and DALI?
DALI-2 is the further developed version of the IEC 62386 series. It also standardises control devices such as push buttons and sensors, and devices are certified by the DALI Alliance, which makes multi-vendor operation easier.
Which HEP drivers can be controlled via DALI?
All DALI dimmable LED drivers from HEP can be selected in the planner. Find the right driver for your LEDs with the LED driver calculator.